首页 | 本学科首页   官方微博 | 高级检索  
     

一起由于套管密封失效导致的220kV变压器故障分析
引用本文:施 逸,周国梁. 一起由于套管密封失效导致的220kV变压器故障分析[J]. 四川电力技术, 2021, 44(5): 87-90
作者姓名:施 逸  周国梁
作者单位:国网四川省电力公司宜宾供电公司,四川 宜宾 644002
摘    要:油浸电容式高压套管在大型变压器上应用十分广泛,承担了载流、绝缘、密封等多项功能。针对一起频繁地震后发生的220 kV变压器匝间短路故障进行了试验检测、解体检查、套管结构分析等,结果表明,故障原因为套管密封结构不合理,在特殊工况下使密封失效。

关 键 词:套管  地震  密封失效  匝间短路

Analysis on 220 kV Transformer Fault Caused by Sealing Failure of Bushing
Shi Yi,Zhou Guoliang. Analysis on 220 kV Transformer Fault Caused by Sealing Failure of Bushing[J]. Sichuan Electric Power Technology, 2021, 44(5): 87-90
Authors:Shi Yi  Zhou Guoliang
Affiliation:State Grid Yibin Electric Power Supply Company
Abstract:Oil immersed capacitive high voltage bushing is widely used in large transformers, which undertakes the functions of carrying current, insulation and sealing. Based on an inter turns short circuit fault of a 220 kV transformer, which happened after a series of earthquakes, the testing detection, disassembly inspection and bushing structure analysis are carried out. The results show that the fault comes from the unreasonable design of the sealing structure of bushing, which fails in special conditions.
Keywords:bushing   earthquake   sealing failure   inter turns short circuit
本文献已被 万方数据 等数据库收录!
点击此处可从《四川电力技术》浏览原始摘要信息
点击此处可从《四川电力技术》下载免费的PDF全文
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号