Raising evaporative cooling potentials using combined cooled ceiling and MPCM slurry storage
Authors:Xichun Wang  Jianlei Niu  AHC van Paassen
Affiliation:1. Department of Building Service Engineering, The Hong Kong Polytechnic University, Kowloon, Hong Kong, PR China;2. Delft University of Technology Process & Energy Laboratory, Leeghwaterstraat 44, 2628 CA Delft, The Netherlands
Abstract:Evaporative cooling is able to generate the cooling medium at a temperature approaching to the ambient wet bulb temperature. In this paper, a low-energy air-conditioning strategy is proposed, which is a combination of cooled ceiling (CC), microencapsulated phase change material (MPCM) slurry storage and evaporative cooling technologies. The assessment of evaporative cooling availability and utilization is done for five representative climatic cities, including Hong Kong, Shanghai, Beijing, Lanzhou and Urumqi in China, and the energy saving potential of the proposed air-conditioning system is analyzed by using a well validated building simulation code. The results indicate that the new system offers energy saving potential up to 80% under northwestern Chinese climate and up to 10% under southeastern Chinese climate. The optimal design method of the slurry storage tank is also proposed based on the slurry cooling storage behaviors and cooling demand variations of the ceiling panels.
Keywords:Evaporative cooling  Thermal energy storage  MPCM slurry  Cooled ceiling  Hybrid system