首页 | 本学科首页   官方微博 | 高级检索  
     


Comparison of impedance based fault location methods for power distribution systems
Authors:J. Mora-Flò  rez,J. Melé  ndez,G. Carrillo-Caicedo
Affiliation:1. Electrical Engineering School, Technological University of Pereira (UTP), La Julita, Pereira, Colombia;2. Electronics, Computer Engineering and Automatics Department, University of Girona (UdG), EPS, Campus Montilivi, 17071 Girona, Spain;3. Electrical Engineering School, Industrial University of Santander (UIS), Cra 27-Cll 9, Bucaramanga, Colombia
Abstract:Performance of 10 fault location methods for power distribution systems has been compared. The analyzed methods use only measurements of voltage and current at the substation. Fundamental component during pre-fault and fault are used in these methods to estimate the apparent impedance viewed from the measurement point. Deviation between pre-fault and fault impedance together with the system parameters are used to estimate the distance to the fault point.
Keywords:Fault location   Impedance based methods   Power distribution systems   Power quality
本文献已被 ScienceDirect 等数据库收录!