首页 | 本学科首页   官方微博 | 高级检索  
     


On-line partial discharge detection in cables
Authors:Ahmed  NH Srinivas  NN
Affiliation:Detroit Edison Co., MI;
Abstract:This paper describes an on-line PD (partial discharge) detection technique applicable to power cables. The method can be applied to both wire screen and solid shielded cables. In wire screen shielded cables, PD components with frequencies <100 MHz can be detected at distances over 150 m from the source, PD activity with levels as low as 20 pC can be detected within 100 m. However, in the case of solid shielded cables, PD levels of ⩾50 pC can be measured within 60 m in the frequency range <50 MHz. This method also can be utilized to check cable accessories such as splices and terminations. PD pulses with frequencies to ~300 MHz can be measured near the joints and terminations. The suitability and the sensitivity of the VHF technique were checked against two other alternative PD detecting techniques (pulse phase analyzer and high speed digital oscilloscope) by performing PD measurements in standard air gap and defects induced in EPR-insulated cable under laboratory-controlled conditions. The suitability and sensitivity of the VHF method were as good as the two alternative PD detection techniques
Keywords:
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号