山火对10~35 kV输电线路安全运行影响试验研究
引用本文:杨佳才,任欣悦,王 勋,张星海,范松海,陈天翔.山火对10~35 kV输电线路安全运行影响试验研究[J].四川电力技术,2022,45(1):1-5.
作者姓名:杨佳才  任欣悦  王 勋  张星海  范松海  陈天翔
作者单位:成都理工大学核技术与自动化工程学院;国网四川省电力公司电力科学研究院
基金项目:国家自然科学区域创新发展联合基金重点支持项目(U19A2080)
摘    要:文中设计搭建了山火对10 kV、35 kV输电线路安全运行影响试验研究平台,燃烧松木、稻草和灌木模拟10 kV、35 kV输电线路下发生山火,研究了山火条件下输电线路三相电压、导线对地泄漏电流、零序电压变化特性;研究分析了火焰高度、火焰宽度对10 kV输电线路绝缘的影响。试验结果表明:山火能引起输电线路单相高阻接地和相间短路;造成单相高阻接地和相间短路是电压等级、对地距离、火焰高度、火焰宽度等多种因素共同作用的结果;火焰是否桥接空气间隙是影响空气绝缘的重要因素。研究了试验过程中出现的输电线路对火焰放电、受火焰影响的某相电压低于其他相电压等现象,得出了山火对10 kV、35 kV输电线路影响原因和规律。

关 键 词:山火  输电线路  运行影响  试验研究

Experimental Research on Influence of Mountain Fire on Safe Operation of 10~35 kV Transmission Lines
YANG Jiacai,REN Xinyue,WANG Xun,ZHANG Xinghai,FAN Songhai,CHEN Tianxiang.Experimental Research on Influence of Mountain Fire on Safe Operation of 10~35 kV Transmission Lines[J].Sichuan Electric Power Technology,2022,45(1):1-5.
Authors:YANG Jiacai  REN Xinyue  WANG Xun  ZHANG Xinghai  FAN Songhai  CHEN Tianxiang
Affiliation:College of Nuclear Technology and Automation Engineering, Chengdu University of Technology;State Grid Sichuan Electric Power Research Institute
Abstract:An experimental research platform for the impact of mountain fire on safe operation of 10 kV and 35 kV transmission lines is designed and established. Pine, straw and shrubs are burnt to simulate the mountain fire fault of 10 kV and 35 kV transmission lines, and the variation characteristics of three-phase voltage, conductor to ground leakage current and zero-sequence voltage of transmission lines under mountain fire are studied. The effects of flame height and flame width on the insulation of 10 kV transmission line are studied and analyzed too. The test results show that mountain fire can cause single-phasehigh resistance grounding and phase to phase short circuit of transmission line, which are the results of the joint action of voltage level, distance to ground, flame height, flame width and other factors, and whether the flame bridges the air gap is an important factor affecting air insulation. The phenomena that the transmission line discharges to the flame and the voltage of one phase affected by the flame is lower than that of other phases during the test are studied, and the causes and laws of mountain fire on 10 kV and 35 kV transmission lines are obtained.
Keywords:wildfire  transmission line  operation effect  experimental research