首页 | 本学科首页   官方微博 | 高级检索  
     

真空断路器操作过电压的限制
引用本文:林挺生,李怀迁.真空断路器操作过电压的限制[J].冶金动力,2001(4):11-14.
作者姓名:林挺生  李怀迁
作者单位:马钢股份公司动力厂,安徽马鞍山,243000
摘    要:选用四星型MOA作为限制真空断路器操作过电压的主保护器,效果十分明显,但选用何种型式的四星型MOA则取决于真空断路器所开断的负荷种类。R-C阻容吸收器作为四星型接法MOA的后备保护器,解决了四星型接法MOA实际存在的放电分散性使保护灵敏度下降问题,改善了过电压波形,降低了避雷器的残压。

关 键 词:真空断路器  操作过电压  电力系统  高压电器  电压限制
修稿时间:2001年11月23

Limitation of Overvoltage of Vacuum Disconnectors in Operation
Lin Tingsheng Li Huaiqian.Limitation of Overvoltage of Vacuum Disconnectors in Operation[J].Metallurgical Power,2001(4):11-14.
Authors:Lin Tingsheng Li Huaiqian
Abstract:The effect was obvious to select four-star connection MOA was a main protector to limit overvoltage in operation of a vacuum disconnector. But, selection of type of the four-star connection MOA depended on kind of load switched off and on by the vacuum disconnector. In actual operation, discharge dispersivity of the four-star connection MOA would reduce sensitivity of protection. R-C absorption device as a spare protector of the four-star connection MOA solved the above problem, improved waveform of the overvoltage and reduced residual voltage of a lightning rod.
Keywords:vacuum disconnector  overvoltage in operation  power system
本文献已被 CNKI 维普 万方数据 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号