Study of cooling system with water mist sprayers: Fundamental examination of particle size distribution and cooling effects |
| |
Authors: | Hideki Yamada Gyuyoung Yoon Masaya Okumiya Hiroyasu Okuyama |
| |
Affiliation: | (1) Graduate School of Environmental Studies, Nagoya University, Furo-cho, Chikusa-ku, Nagoya-shi, Aichi 464-8603, Japan;(2) Institute of Technology, Shimizu Corporation, 3-4-17, Etchujima, Koto-ku, Tokyo 135-8530, Japan |
| |
Abstract: | A cooling system that sprays micro water droplets could prove useful in mitigating temperature increases in urban areas by using the heat of water evaporation, a process that consumes only small amounts of water and energy. If water mist is sprayed in a semi-outdoor area, for example, under a canopy, it could potentially improve conditions on hot days. However, there is little reference data concerning the design or control of such systems. In order to propose a method for designing and predicting the performance of a water mist system, we discuss differences in cooling effects in the context of particle size distribution of water mist. The results of numerical fluid analysis showed there is no significant difference in temperature reduction for different particle sizes. However, the water particles remained in a lower position with larger particles. |
| |
Keywords: | water mist evaporative cooling urban heat island numerical fluid analysis |