首页 | 本学科首页   官方微博 | 高级检索  
     

永磁直驱风电全功率变流器并联控制方法研究
引用本文:毛荀,郭力,彭红英,占勇.永磁直驱风电全功率变流器并联控制方法研究[J].电源学报,2023,21(4):122-129.
作者姓名:毛荀  郭力  彭红英  占勇
作者单位:国网安徽省电力有限公司电力科学研究院,国网安徽省电力有限公司电力科学研究院,中国电力科学研究院有限公司,国家电网仿真中心,国网安徽省电力有限公司电力科学研究院
基金项目:国家重点研发计划资助项目(基金编号2016YFB0900400) 项目名称:分布式可再生能源发电集群并网消纳关键技术及示范
摘    要:为提高永磁直驱风电全功率变流器并联控制效果,提出永磁直驱风电全功率变流器并联控制方法研究。首先分析永磁直驱风电全功率变流器拓并联扑结构,建立永磁直驱风电全功率变流器模型,计算无功功率受有功功率波动造成电压幅值产生波动,结合虚拟阻抗使功率在此种情况下耦合,系统总电阻补偿至0时,实现永磁直驱风电全功率变流器并联控制。实验结果表明,采用该方法控制永磁直驱风电全功率变流器并联运行的机侧环流与网侧环流波动较为稳定,验证了该方法的控制性能。

关 键 词:虚拟阻抗  永磁  直驱  风电全功率变流器  并联  控制方法
收稿时间:2020/9/24 0:00:00
修稿时间:2023/4/27 0:00:00

Research on Parallel Control Method for Permanent Magnet Direct-drive Wind Power Full-power Converter
MAO Xun,GUO Li,PENG Hongying,ZHAN Yong.Research on Parallel Control Method for Permanent Magnet Direct-drive Wind Power Full-power Converter[J].Journal of power supply,2023,21(4):122-129.
Authors:MAO Xun  GUO Li  PENG Hongying  ZHAN Yong
Affiliation:State Grid Anhui Electric Power Research Institute,,,
Abstract:In order to improve the parallel control effect of permanent magnet direct drive wind power full power converter, the parallel control method of permanent magnet direct drive wind power full power converter is proposed. Firstly, the topology parallel topology structure of permanent magnet direct drive wind power full power converter is analyzed, and the model of permanent magnet direct drive wind power full power converter is established. The voltage amplitude fluctuation of reactive power caused by active power fluctuation is calculated. Combined with virtual impedance, the power is coupled in this case. When the system total resistance is compensated to 0, the parallel control of permanent magnet direct drive wind power full power converter is realized. The experimental results show that the fluctuation of the circulating current at the generator side and the circulating current at the grid side of the parallel operation of the permanent magnet direct drive wind power converter controlled by this method are relatively stable, which verifies the control performance of the method.
Keywords:Virtual impedance  permanent magnet  direct drive  wind power full power converter  parallel  control method
点击此处可从《电源学报》浏览原始摘要信息
点击此处可从《电源学报》下载免费的PDF全文
设为首页 | 免责声明 | 关于勤云 | 加入收藏