首页 | 本学科首页   官方微博 | 高级检索  
     


The method of testing of XLPE cable insulation resistance to partial discharges and electrical treeing
Authors:M Jevtic  A M Andreev
Affiliation:(1) Technical faculty in Bor, University of Belgrade, 19210 Bor, Yugoslavia;(2) Electro-mechanical faculty, Saint-Petersburg Technical University, Saint-Petersburg, Russia
Abstract:The paper gives a method of model XLPE medium voltage cable insulation testing for partial discharges and electrical treeing with a point to plane test geometry. Based on this method, a comparative estimate of insulation resistance to treeing and partial discharges have been made. XLPE crosslinked by different methods (steam medium and hot nitrogen medium) and with varying contents of inorganic filler kaolin were tested. The characteristics of partial discharges were measured by means of a pulse height analyser characterized with a microscope. The data have been analysed statistically.
Keywords:Electrical treeing  partial discharges  XLPE cable insulation
本文献已被 SpringerLink 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏