电缆外护套环流分布在线监测系统的研制(英文)
引用本文:孟永鹏,彭发东,闫力. 电缆外护套环流分布在线监测系统的研制(英文)[J]. 高电压技术, 2009, 35(3): 533-538
作者姓名:孟永鹏  彭发东  闫力
作者单位:State;Laboratory;Electrical;Insulation;Power;Equipment;Xi’an;Jiaotong;University;
基金项目:国家高技术研究发展计划(863计划) 
摘    要:
The value of metal sheath’s circulating current of cross-linked power cables is very small in ideal condition, but the value is not so small that the circulating current can’t be ignored because of various factors in actual running condition. The circulating current method can judge whether the multipoint earthing fault happens by monitoring the variety of metal sheath’s circulating current value. This article introduces an on-line monitoring system which uses the circulating current method to monitor the multipoint earthing fault of the metal sheath. In the hardware layer, we use distributed current sensors and microcontroller’s acquisition units to complete the signal acquisition and signal conditioning of the circulating current value. After the distributed acquisition and conditioning, the signals, through the RS485 bus, will be sent to the Ethernet Serial Device Server network system and then connected to the console cabinet. The computer of the console cabinet could read the circulating current value on-line by the Real Com Mode of the Ethernet Serial Device Server. This distributed on-line monitoring system has a simple structure, excellent real-time performance and high reliability proved by the practical operation.

关 键 词:cross-linked  power cable  distributed system  circulating current  on-line monitoring  XLPE

Distributed On-line Monitoring System for Sheath Circulating Current of Cross-linked Power Cables
MENG Yong-peng ,PENG Fa-dong,YAN Li,CHEN Xiao-lin,CHENG Yong-hong,LIU Jing. Distributed On-line Monitoring System for Sheath Circulating Current of Cross-linked Power Cables[J]. High Voltage Engineering, 2009, 35(3): 533-538
Authors:MENG Yong-peng   PENG Fa-dong  YAN Li  CHEN Xiao-lin  CHENG Yong-hong  LIU Jing
Affiliation:MENG Yong-peng 1,PENG Fa-dong1,YAN Li1,CHEN Xiao-lin1,CHENG Yong-hong1,LIU Jing2
Abstract:
The value of metal sheath's circulating current of cross-linked power cables is very small in ideal condition, but the value is not so small that the circulating current can't be ignored because of various factors in actual running condition. The circulating current method can judge whether the multipoint earthing fault happens by monitoring the variety of metal sheath's circulating current value. This article introduces an on-line monitoring system which uses the circulating current method to monitor the muhipoint earthing fault of the metal sheath. In the hardware layer, we use distributed current sensors and microcontroller's acquisition units to complete the signal acquisition and signal conditioning of the circulating current value. After the distributed acquisition and conditioning, the signals, through the RS485 bus, will be sent to the Ethernet Serial Device Server network system and then connected to the console cabinet. The computer of the console cabinet could read the circulating current value on-line by the Real Corn Mode of the Ethernet Serial Device Server. This distributed on-line monitoring system has a simple structure, excellent real-time performance and high reliability proved by the practical operation.
Keywords:cross-linked  power cable  distributed system  circulating current  on-line monitoring  XLPE