首页 | 本学科首页   官方微博 | 高级检索  
     

智能变电站稳定控制装置数字采样的设计与实现
引用本文:程维杰,王计林,马刚,刘金生,翁毅选. 智能变电站稳定控制装置数字采样的设计与实现[J]. 电力工程技术, 2020, 39(2): 173-177
作者姓名:程维杰  王计林  马刚  刘金生  翁毅选
作者单位:南方电网深圳电力局有限公司;国电南瑞科技股份有限公司;南京师范大学,国电南瑞科技股份有限公司,南京师范大学,南方电网深圳电力局有限公司,南方电网深圳电力局有限公司
基金项目:国家自然科学基金资助项目(51607093)
摘    要:在智能变电站中,电网安全稳定控制装置作为跨间隔设备,需要同时接收、处理多个间隔的采样量。针对稳定控制装置“直采”模式下多间隔采样同步问题,提出了基于本地时标的同步和重采样插值合并处理的方法。以本地时标为基准,借助系统提供的辅助时钟,以重采样间隔对采样数据进行同步和线性插值重采样,并对线性插值误差进行分析。最后,依托FPGA+DSP硬件平台实现了稳控装置的数字化采样,并搭建试验系统,从采样精度和同步有效性方面对文中提出的基于本地时标的同步重采样插值算法的时效性和可行性进行验证,试验结果验证了基于本地时标的同步线性重采样方法能够满足稳定控制装置实际工程对实时性和精度要求。

关 键 词:智能变电站  稳定控制装置  多间隔采样  同步采样  线性插值
收稿时间:2018-07-10
修稿时间:2019-10-12

Stability control device digital sampling in smart substation
CHENG Weijie,WANG Jilin,MA Gang,LIU Jinsheng,WENG Yixuan. Stability control device digital sampling in smart substation[J]. Electric Power Engineering Technology, 2020, 39(2): 173-177
Authors:CHENG Weijie  WANG Jilin  MA Gang  LIU Jinsheng  WENG Yixuan
Affiliation:(China Southern Power Grid Co., Ltd,NARI Technology Co., LTD,Nanjing Normal University,China Southern Power Grid Co., Ltd,China Southern Power Grid Co
Abstract:In smart substation, the stability control device as a cross-interval device needs to receive and process a plurality of spaced sampling quantities simultaneously. Aiming at the problem of multi-interval sampling synchronization in "direct sampling ", this paper proposes a synchronization and resampling interpolation combining processing method based on local time scale. In this paper, the message time stamp is used as the stability control device in the "direct sampling " for multi-interval sampling synchronization and resampling reference. With the auxiliary clock, the sampling data is synchronized, resampling by linearly interpolated and analyzed the interpolation error. Finally, the digital sampling of the stability control device is realized by FPGA+DSP hardware platform, and the experimental system is built. The timeliness of the local time-scale based synchronization interpolation algorithm proposed in this paper is analyzed from the aspects of sampling accuracy and synchronization effectiveness. The feasibility is verified. The test results verify that the synchronous linear resampling based on local time scale can meet the real-time and accuracy requirements of the actual engineering of the stability control device.
Keywords:Smart Substation   Stability Control Device   Cross-interval Sampling   Sample Synchronized   Interpolation Algo-rithm  
本文献已被 CNKI 维普 等数据库收录!
点击此处可从《电力工程技术》浏览原始摘要信息
点击此处可从《电力工程技术》下载免费的PDF全文