Voltage Distribution among the Coils and Turns of a Form Wound AC Rotating Machine Exposed to Impulse Voltage
Authors:Sharma  DK Rhudy  RG Owen  EL
Affiliation:Electric Power Research Institute, Palo Alto, California;
Abstract:This paper describes a method of calculating voltage distribution in a stator winding exposed to impulse voltage. In this method, the voltage distribution in an equivalent-circuit representation of the stator winding is calculated. The winding is treated as an infinite number of identical coils connected in series, with each coil represented by an equivalent circuit including inductance, turn-to-ground capacitance and conductance, and with mutual inductance, capacitance, and conductance between turns. The impulse voltage is approximated by a Fourier series of components. The voltage distribution for each component is calculated, and the complete voltage distribution is obtained by summing the voltages due to each component. The complete calculating procedure, including the calculation of the equivalent circuit parameters has bee programmed in Basic language for computer calculation. Examples of the coil and turn voltages distributions calculated by this program and a comparison of calculated data with test data for a particular stator winding are included.