首页 | 本学科首页   官方微博 | 高级检索  
     

设备故障对同一变电站多套串补过电压保护装置参数的影响
引用本文:唐金昆,李欣,汪扬,许海,刘慧文.设备故障对同一变电站多套串补过电压保护装置参数的影响[J].现代电力,2014,31(5):85-89.
作者姓名:唐金昆  李欣  汪扬  许海  刘慧文
作者单位:1.南方电网超高压输电公司检修试验中心,广东广州 510063 ;
摘    要:在进行串补过电压保护设备参数设计时,一般只考虑不同的系统运行工况、不同的故障类型及故障时刻等系统因素,而很少考虑串补设备故障的影响,但在实际运行中串补设备故障的工况是存在的,而且对串补设备参数有直接影响。本文以南方电网百色串补站3套串补装置为例,利用最新电网数据及3套串补的设备参数和过电压保护配置,建立串补设备检修、保护误动及拒动等特殊工况模型,研究了在串补间隙误触发、拒触发、串补检修退出3种设备故障工况下,同一变电站多套串补之间参数的相互影响,并进行仿真分析。研究表明在进行串补主设备参数设计时,应适当考虑一套串补设备故障对其他串补过电压保护装置参数的影响。

关 键 词:串补    参数配合    过电压保护    参数适应性    金属氧化物限压器
收稿时间:2013-10-11

Effect of Equipment Faults on Over-voltage Protection Parameters of Multiple Series Compensation Devices in the Same Substation
TANG Jinkun,LI Xin,WANG Yang,XU Hai,LIU Huiwen.Effect of Equipment Faults on Over-voltage Protection Parameters of Multiple Series Compensation Devices in the Same Substation[J].Modern Electric Power,2014,31(5):85-89.
Authors:TANG Jinkun  LI Xin  WANG Yang  XU Hai  LIU Huiwen
Affiliation:1.Test and Maintenance Center,CSG EHV Power Transmission Company, Guangzhou 510063, China;2.China EPRI Science & Technology CO., Ltd. of State Grid Smart Grid Research Institute, Beijing 102200, China
Abstract:In general, only such system factors as different system operation conditions, different fault types and fault time are considered when over-voltage protection parameters for series compensation (SC) devices are designed, while the influence of SC device fault is seldom considered. But in fact, the cases of SC device faults exist in practical operation, which directly influence the SC device parameters. In this paper, by using the current data of China Southern Grid and parameters of three sets of series compensation (SC) devices in Baise substation and their protection configurations, the models of overhaul of SC and false action of over-voltage protection are established. The interaction influence between parameters of SC devices in the same substation are studied in such operation conditions as false trigger and refusing trigger of GAP, and SC device out of service. Study results show that it is reasonable to consider the effect of a set of SC faults on parameters of other SC over-voltage protection devices when carrying out SC basic design.
Keywords:series capacitor (SC)  parameter cooperation  over-voltage protection  parameter adaptability  MOV
本文献已被 CNKI 万方数据 等数据库收录!
点击此处可从《现代电力》浏览原始摘要信息
点击此处可从《现代电力》下载全文