Abstract: | Transient stability may be seriously affected when a large number of distributed generators (DG) stop simultaneously during voltage sag. It is necessary to analyze accurately the dynamics of bulk power systems with high DG penetration. In this paper, transient stability is studied by analyzing power‐angle curves of generators while considering load dynamics and model order reduction at lower voltages. Based on the analysis, a decrease in the load internal resistance after voltage sag causes transient instability of generators. The phenomenon is confirmed through simulation using a one‐machine and one‐load model. This paper also suggests that the simulation results might be misled by traditional bulk power system modeling such as using the static load model and ignoring impedance at lower voltages. As for the numerical simulation, a large level of DG stoppage leads to transient step out in a bulk power system, and the stability is greatly improved by DG voltage regulation. © 2007 Wiley Periodicals, Inc. Electr Eng Jpn, 162(2): 20– 29, 2008; Published online in Wiley InterScience ( www.interscience.wiley.com ). DOI 10.1002/eej.20608 |