Results of experimental and theoretical studies of the azeeotropic refrigerant R507
Authors:R Döring  H Buchwald  J Hellmann
Affiliation:aFachhochschule Münster - Steinfurt, Germany;bSOLVAY Fluor und Derivate GmbH, Postfach 220, D-30002 Hannover, Germany
Abstract:For a blend containing R143a and R125 (View the MathML source by weight), thermodynamic data like vapour pressures, liquid densities, as well as the volumetric behaviour of the gaseous phase, have been experimentally measured and mathematically correlated. This refrigerant blend shows azeotropic behaviour and is known as R507 according to the ASHRAE nomenclature. For use in refrigeration and air-conditioning units in low and medium temperature applications, R507 is a suitable refrigerant. Test results based on measurements from a refrigeration installation have shown that similar operating parameters can be achieved in comparison to R502. The compressor discharge temperatures, pressure ratios and coefficients of performance compare well to the traditionally used azeotropic refrigerant R502. Further, the tests have shown that on average the refrigerating capacities of R507 are approximately 5–6% higher than the capacities of R502.
Keywords:thermodynamic data  R507  performance tests  comparison to R502