首页 | 本学科首页   官方微博 | 高级检索  
     


Replacement of R22 in tube-and-shell condensers: experiments and simulations
Authors:Cecilia Gabrielii  Lennart Vamling
Affiliation:Department of Heat and Power Technology, Chalmers University of Technology, S-412 96 Göteborg, Sweden Tel: +46-31-7723013; Fax: +46-31-821928
Abstract:An investigation of the change in condenser overall heat transfer coefficient when replacing R22 with one of the three mixtures R407C, R404A and R410B was made, both experimentally and theoretically. Measurements have been carried out on a full-scale test plant consisting of a horizontal shell-side condenser. According to the measurements the decrease in overall heat transfer coefficient for the non-azeotropic mixture R407C was very large, up to 70% compared to R22, while for the near-azeotropic mixture R404A the decrease was less than 15%. Simulations of the condenser were done with a comprehensive computer program, calculating the condensation heat transfer with an approximate method including a correction for mass resistance. The calculation model was not able to predict this large degradation for the non-azeotropic mixture, while the predictions agreed rather well with the measurements for the pure fluid and the near-azeotropic mixtures.
Keywords:heat transfer  condenser  regrigerant  R22  substitute  R407C  R404A  R410B  performance  calculation  measurement
本文献已被 ScienceDirect 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号