基于MEEMD的配电网故障选线方法研究
引用本文:阚哲,杨凡,韩景宇,孙震,吴东旭.基于MEEMD的配电网故障选线方法研究[J].辽宁石油化工大学学报,2021,41(2):79.
作者姓名:阚哲  杨凡  韩景宇  孙震  吴东旭
作者单位:1.辽宁石油化工大学 信息与控制工程学院,辽宁 抚顺 113001; 2.中国石油管道有限责任公司 西气东输分公司,上海 200122; 3.国网山东电力公司 东阿县供电公司,山东 聊城 252200; 4.中国石油化工集团公司 巴陵分公司,湖南 岳阳 414000; 5.国网吉林电力公司 白城市供电公司,吉林 白城 137000
基金项目:辽宁省教育厅一般项目(L2020019)。
摘    要:针对暂态零序电流特征频段内含有过少的频率分量以及无较高幅值的低频分量而给配电网故障选线带来的困扰,利用改进的集合经验模态分解(MEEMD)方法解决选线准确率低的问题。首先,考虑配电网引入分布式电源后对线路零序电流的影响;然后,利用MEEMD将故障后的零序电流按照频率大小分解成多个频率信号,得到本征模态函数并提取其最高频成分;最后,通过分析最高频率的信号波形得出选线结果。该过程不需要基信号,从而使得到的信号特性更接近原信号。结果表明,该方法可有效提高故障选线的准确率。

关 键 词:故障选线    零序电流    分布式电源    改进的集合经验模态分解    接地故障  
收稿时间:2019-12-27

Research on Fault Line Selection Method of Distribution Network Based on MEEMD
Kan Zhe,Yang Fan,Han Jingyu,Sun Zhen,Wu Dongxu.Research on Fault Line Selection Method of Distribution Network Based on MEEMD[J].Journal of Liaoning University of Petroleum & Chemical Technology,2021,41(2):79.
Authors:Kan Zhe  Yang Fan  Han Jingyu  Sun Zhen  Wu Dongxu
Affiliation:1.School of Information and Control Engineering,Liaoning Petrochemical University,Fushun Liaoning 113001,China; 2.China National Petroleum Corporation Pipeline Co., Ltd. West?East Gas Transmission Branch, Shanghai 200122,China; 3.The Power Supply Company of Donge County,Liaocheng Shandong 252200,China; 4.China Petrochemical Corporation Baling Branch,Yueyang Hunan 414000,China; 5.The Power Supply Company of Baicheng,Baicheng Jilin 137000,China
Abstract:To solve the problem of distribution network fault line selection caused by too few frequency components and no high amplitude low frequency components in the characteristic frequency band of transient zero sequence current, an improved ensemble empirical mode decomposition (MEEMD) method is proposed. Firstly, the influence of distributed generation on line zero sequence current was considered; then, the zero sequence current after fault was decomposed into multiple frequency signals according to frequency by meemd, and the eigenmode function was obtained and the highest frequency component is extracted; finally, the line selection result was obtained by analyzing the signal waveform of the highest frequency. The basic signal was not needed in this process, so the characteristics of the obtained signal were closer to the original signal. The process of fault line selection based on meemd was described in detail, and the influence of multi scene distribution network considering distributed generation on fault line selection is discussed. The simulation results show that the method can effectively improve the accuracy of fault line selection.
Keywords:Fault line selection  Zero?sequence current  Distributed generation  MEEMD  Ground fault  