首页 | 本学科首页   官方微博 | 高级检索  
     


Results of lightning impulse tests for a 275‐kV full GIS substation
Authors:Ryosuke Hatano  Yasuhisa Ishikawa  Toshiaki Ueda  Kenichi Nojima  Hideki Motoyama
Abstract:This paper describes the outline and results of the lightning impulse tests for a 275‐kV full GIS substation. The behavior of lightning surges is a very important factor for the rational design of substations and low‐voltage and control circuits inside the substations. For the above reason, we carried out lightning impulse tests for a new 275‐kV full GIS substation. In these tests, we measured voltage induced in low‐voltage and control circuits, transient characteristics of grounding grid, injected voltage and current waveforms, and so on. By investigating these data, we confirmed the behavior of lightning surges inside the substation. We also compared simulated waveforms by EMTP analysis with the measured waveforms. The simulated results agreed well with the measured results. © 2003 Wiley Periodicals, Inc. Electr Eng Jpn, 146(1): 46–58, 2004; Published online in Wiley InterScience ( www.interscience.wiley.com ). DOI 10.1002/eej.10230
Keywords:lightning surge  275‐kV full GIS substation  grounding resistance  control circuit
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号