Resistance varying characteristics of DC superconducting fault current limiter in MTDC system
Affiliation:1. School of Electrical Engineering, Wuhan University, Wuhan 430072, PR China;2. Electric Power Research Institute, State Grid Chongqing Electric Power Company, Chongqing 401123, PR China;3. School of Electrical and Electronic Engineering, Huazhong University of Science and Technology, Wuhan 430074, PR China
Abstract:Recent years, voltage source converter-based multi-terminal high voltage DC power transmission (MTDC) is widely developed in the world. However, it is difficult for the existing DC breaker to cut off the fault transmission line with large short-circuit fault current. Then, it would be helpful to develop DC fault current limiter for the MTDC system. In this paper, DC superconducting fault current limiter (DCSFCL) is proposed to limit fault current. In order to study the resistance-time performance of the DCSFCL under the rapid change of fault current, a simulation model of Zhoushan MTDC system with DCSFCL is established, and the current-limiting performance of the DCSFCL at different location of the grid is studied. The simulation results show that DCSFCL can effectively limit short-circuit current and improve the operation reliability of MTDC system.
Keywords:Superconducting fault current limiter  MTDC  Reactor  DC fault current  Short-circuit fault
本文献已被 ScienceDirect 等数据库收录!