真空灭弧室主屏蔽罩电位静态测量分析
引用本文:王承玉,王季梅.真空灭弧室主屏蔽罩电位静态测量分析[J].高压电器,1993,29(4):28-30.
作者姓名:王承玉  王季梅
作者单位:西安交通大学 710049 (王承玉),西安交通大学 710049(王季梅)
摘    要:对中间封装式和瓷柱支撑式两种主屏蔽罩安装方式的真空灭弧室中主屏蔽罩电位进行了静态工频测试,找出了为什么中封式真空灭弧室装入整机后并不比瓷柱式真空灭弧室耐压特性优越的原因,指出在真空断路器设计中,尤其在高电压等级下,真空灭弧室的均压问题应与整机总体设计同时考虑。

关 键 词:真空灭弧室  屏蔽  电势  测量  分析

Static Potential Measurement on the Shield of Vacuum Interrupters
Wang Chengyu,Wang Jimei.Static Potential Measurement on the Shield of Vacuum Interrupters[J].High Voltage Apparatus,1993,29(4):28-30.
Authors:Wang Chengyu  Wang Jimei
Abstract:This Paper measures the static potential in vapour shields of two fixing methods-middle fixed type and ceramic supporters fixed type.It finds out the reasons Thy the middle fixed type is not better than the ceramic fixed one in voltage characteristic when it is fixed into the switchge-ar,It points out that it is.necessary to co.mbine the design of vacuum interrupter with switchgear,especially under high voltage level.
Keywords:vacuum interrupter  shield  potential  measurement  analysis  