首页 | 本学科首页   官方微博 | 高级检索  
     


Compartment fire near-field entrainment measurements
Authors:N A Dembsey  P J Pagni  R B Williamson
Affiliation:

College of Engineering, University of California at Berkeley, Berkeley, CA 94720, USA

Abstract:A widely accepted consensus on entrainment models for large fires in compartments does not yet exist. To obtain further information on such entrainment rates, 20 full-scale, near-field experiments were conducted. Near-field entrainment occurs when hot layer interface heights are beneath the burner mean flame height so that cold layer entrainment occurs only near the burner surface. A durable compartment, similar to the standard fire test compartment, was designed and used in conjunction with a 0·61 m × 1·22 m porous surface propane burner to produce compartment fires with heat release rates from 330 to 980 kW. Entrainment rates of 0·74–0·98 kg/s were calculated from temperature measurements made within the compartment and in the doorway. The entrainment rates determined here were correlated with values from the literature. This correlation led to two curve fits which modify Zukoski's far-field offset model and can be used to estimate near-field entrainment rates. An offset for the near-field model of Thomas was also developed. The fire plume model of Baum and McCaffrey was found to compare favorably with the entrainment rates determined here.
Keywords:
本文献已被 ScienceDirect 等数据库收录!