Abstract:Large confined space has high incidence of fires, which seriously threatens the safety of people working there. Understanding the distribution of smoke in such large space is critical to fire development prediction and smoke control. Three improved methods for the stratification interface prediction of fire smoke are developed, including of improved intra-variance, integral ratio and N-percentage methods. In these methods, the interface height is determined by the vertical temperature distribution based on a three-layer smoke zone model, which is an improvement of a two-layer zone model. Thereafter, the three improved methods are applied to several typical fire cases simulated CFD to predict the smoke interface, and their applicability and reliability are verified by comparison of the smoke stratification results with the filed simulation results. Results show that the three improved methods can effectively determine the location of the three-layer zone model's interface, and they have the ability to predict smoke interface for fires with different fire source types and ventilation conditions.
Keywords:fire safety  three-layer zone model  large space  smoke interface