Smoke control based on a solar-assisted natural ventilation system |
| |
Affiliation: | 1. Department of Architecture and Civil Engineering, City University of Hong Kong, Hong Kong SAR, PR China;2. National United Engineering Laboratory of Integrated and Intelligent Transportation, School of Transportation and Logistics, Southwest Jiaotong University, Chengdu, 610031, PR China |
| |
Abstract: | The possibility of using the same system for natural ventilation and smoke control is examined. As an example, a prototype building is proposed. The proposed prototype is an eight-storey building with a solar chimney on top of the atrium. Reduced scale model experiments and Computational fluid dynamics analysis are conducted. As a result, when the area ratio of outlet to inlet is greater than 2, air change rate of the utility space reaches over 2 times per hour and in an event of a fire breaking out in the atrium, the neutral pressure plane of the smoke layer stays inside the chimney. Smoke infiltration into adjacent spaces used for evacuation is prevented. |
| |