首页 | 本学科首页   官方微博 | 高级检索  
     

(12期拿下)SSSC阻尼系统功率振荡的控制器设计
引用本文:李娟,赵磊.(12期拿下)SSSC阻尼系统功率振荡的控制器设计[J].电测与仪表,2017,54(13).
作者姓名:李娟  赵磊
作者单位:东北电力大学 电气工程学院,吉林 吉林,132012
摘    要:阻尼系统的功率振荡是静止同步串联补偿器(SSSC)重要的作用之一。考虑了SSSC内部动态的变化过程,即控制器的输出电压幅值与相角变化及直流侧电容动态调节过程,在此基础上建立SSSC的动态模型。推导脉冲宽度调制系数变化量与电角速度变化量之间的关系得到控制系统的传递函数,通过对控制系统中的参数控制从而对SSSC进行控制,而控制系统的参数是通过人工蜂群(ABC)的优化过程进行调整的。该优化方法以角速度差为目标,通过不断迭代更新,最后得到控制系统控制参数的最优解。在MATLAB中搭建模型,通过与传统PI控制仿真效果进行对比,通过优化方法能够有效快速的调整控制参数,从而更好地调节SSSC等效注入电压,有效地提高输电线路传输有功功率的能力,快速抑制系统功率振荡。

关 键 词:静止同步串联补偿器  控制系统传递函数  人工蜂群算法  阻尼功率振荡
收稿时间:2016/6/24 0:00:00
修稿时间:2016/8/1 0:00:00

Design of SSSC Auxiliary Controller for Damping System Power Oscillation
LI Juan and ZHAO Lei.Design of SSSC Auxiliary Controller for Damping System Power Oscillation[J].Electrical Measurement & Instrumentation,2017,54(13).
Authors:LI Juan and ZHAO Lei
Affiliation:Electrical Engineering College,Northeast Dianli University,Jilin Jilin 132012,Electrical Engineering College,Northeast Dianli University,Jilin Jilin 132012
Abstract:One of the most important functions of static synchronous series compensator (SSSC) is power oscillation damping system.Considering the change process of SSSC internal dynamics, namely the dynamic adjustment process among output voltage amplitude of controller, phase angle changes and the DC side capacitor, on this basis, the SSSC dynamic model is established.The control system transfer function is obtained by deriving the relationship of pulse width modulation coefficient with the amount of change in the electrical angular velocity variation, by controlling the parameters of the control system, and thus achieving SSSC controls, and optimization process of adjustment of parameters in control system achieves by artificial bee colony (ABC).The optimization method takes angular velocity difference as the goal, through continuous iterative update, and finally gets the optimal solution of parameters in control system.Built in MATLAB model, comparing with the conventional PI control simulation results, the proposed optimization method can effectively and quickly adjust control parameters, and then, regulate the SSSC equivalent injection voltage in a better way, which effectively improves the active power transmission capacity in transmission line, and suppresses the system power oscillation in a fast way.
Keywords:static synchronous series compensator  control system transfer function  artificial bee colony algorithm  damping power oscillation
本文献已被 CNKI 万方数据 等数据库收录!
点击此处可从《电测与仪表》浏览原始摘要信息
点击此处可从《电测与仪表》下载全文