Audible noise and vibration characteristics of DC-bias in power transformers caused by urban mass transit system
WU Xiaowen,Zhou Nianguang,Hu Sheng,Peng Jiwen and Lu Ling. Audible noise and vibration characteristics of DC-bias in power transformers caused by urban mass transit system[J]. Electrical Measurement & Instrumentation, 2017, 54(17)
Authors:WU Xiaowen  Zhou Nianguang  Hu Sheng  Peng Jiwen  Lu Ling
Affiliation:State Grid Hunan Electric Power Corporation Research Institute,State Grid Hunan Electric Power Corporation Research Institute,State Grid Hunan Electric Power Corporation Research Institute,State Grid Hunan Electric Power Corporation Research Institute,State Grid Hunan Electric Power Corporation Research Institute
Abstract:DC-bias mechanism of power transformer caused by urban mass transit system is investigated in this paper . The monitoring of field audible noise and vibration measurement of power transformer is carried out in DC-bias condi-tion.The noise and vibration characteristics of power transformer before and after DC-bias are analyzed , from which the characteristic parameter of DC-bias is extracted .Time variation of the characteristic parameter is compared with that of the power transformer noise and vibration .The result shows that the occurrence of DC-bias is relevant with the regular operation state of the urban mass transit system .The signals of audible noise , vibration and direct current of the power transformer have the same variation process when DC-bias occurs.The rate of odd-to-even-order harmonic of the noise and vibration signals is obviously increased compared with that in normal condition .Therefore , it could be effectively applied in the DC-bias condition evaluation of power transformers .
Keywords:urban mass transit system  power transformer  DC-bias  audible noise  vibration