首页 | 本学科首页   官方微博 | 高级检索  
     

基于站域信息的同杆双回线接地距离保护优化方案
引用本文:高厚磊,刘益青,王兴国,黄家凯,徐明阳. 基于站域信息的同杆双回线接地距离保护优化方案[J]. 电力自动化设备, 2021, 41(3): 49-56. DOI: 10.16081/j.epae.202012011
作者姓名:高厚磊  刘益青  王兴国  黄家凯  徐明阳
作者单位:山东大学 电气工程学院,山东 济南 250061;济南大学 自动化与电气工程学院,山东 济南 250022;中国电力科学研究院有限公司,北京 100192;山东大学 电气工程学院,山东 济南 250061;济南大学 自动化与电气工程学院,山东 济南 250022
基金项目:中国电力科学研究院有限公司科技项目(基于站域信息对变电站后备保护原理性能提升研究)(SGDK0000JBJS1907459)
摘    要:基于单间隔电气量的接地距离保护由于受到同杆双回线线间互感的影响,存在故障线路距离测量不准确、非故障线路易发生反方向误动和末端故障超越等问题.利用智能变电站中跨间隔站域信息高度共享的特点,构建了同杆双回线单元式保护配置方案,设计了过程层信息获取及交互的实现方案.利用双回线的断路器位置和接地刀闸位置信息自适应地选择零序补偿...

关 键 词:站域信息  同杆双回线  接地距离保护  故障选相  配置方案

Optimization scheme of grounding distance protection based on substation-area information for double-circuit transmission lines on same tower
GAO Houlei,LIU Yiqing,WANG Xingguo,HUANG Jiakai,XU Mingyang. Optimization scheme of grounding distance protection based on substation-area information for double-circuit transmission lines on same tower[J]. Electric Power Automation Equipment, 2021, 41(3): 49-56. DOI: 10.16081/j.epae.202012011
Authors:GAO Houlei  LIU Yiqing  WANG Xingguo  HUANG Jiakai  XU Mingyang
Affiliation:School of Electrical Engineering, Shandong University, Jinan 250061, China;School of Electrical Engineering, University of Jinan, Jinan 250022, China;China Electric Power Research Institute, Beijing 100192, China
Abstract:Due to the influence of mutual inductance between double-circuit transmission lines on same tower, the grounding distance protection based on single interval electrical quantity has some problems, such as inaccurate distance measurement of fault lines, reverse direction misoperation of non-fault lines and terminal fault override. Based on the characteristics of information sharing between different bays in the smart substation, a unit configuration scheme of double-circuit transmission lines on same tower is constructed. The realization scheme of information acquisition and interaction at the process layer is designed. The zero-sequence compensation coefficient is adaptively selected by using the circuit breaker position and the grounding switch position of the double-circuit transmission lines. The fault line and fault phase are selected based on six-phase current information of double-circuit transmission lines and six-sequence component method, and the zero-sequence current self-adaptive compensation of the adjacent line for grounding distance protection is realized according to the line selection results, while the zero-sequence current compensation of the adjacent line is no longer used for the non-fault line. Theoretical analysis and digital simulation show that the proposed scheme of unit configuration and grounding distance protection can realize the zero-sequence current self-adaptive compensation of the adjacent line in double-circuit transmission lines, and solve the problem of reverse direction misoperation of non-fault lines caused by the blind zero-sequence current compensation of adjacent line.
Keywords:substation-area information   double-circuit transmission lines on same tower   grounding distance protection   fault phase selection   configuration scheme
本文献已被 CNKI 万方数据 等数据库收录!
点击此处可从《电力自动化设备》浏览原始摘要信息
点击此处可从《电力自动化设备》下载全文
设为首页 | 免责声明 | 关于勤云 | 加入收藏