国家大剧院观众厅空调系统和气流组织方式的设计和分析 |
| |
引用本文: | 孙敏生,王威,万水娥. 国家大剧院观众厅空调系统和气流组织方式的设计和分析[J]. 暖通空调, 2003, 33(3): 1-8 |
| |
作者姓名: | 孙敏生 王威 万水娥 |
| |
作者单位: | 北京市建筑设计研究院 |
| |
摘 要: | 介绍了观众厅座椅下送风方案。通过对置换通风和空调系统下送风方式的分析和实测,总结出这种气流组织的设计计算方法。全年能耗分析显示,为达到高标准的卫生和舒适要求采用30m^3/h人均新风量的椅下送风空调方式,比15m^3/h人均新风量的混风变新风比空调系统制冷量增加50.9%。
|
关 键 词: | 国家大剧院 观众厅 空调系统 气流组织 设计 置换通风 送风 |
修稿时间: | 2003-03-17 |
Design analysis of air conditioning and air distribution in the auditoria of the national theatre |
| |
Abstract: | Describes the under-seat air supply mode adopted in the project. Provides a procedure of design and calculation based on analyses and field measurement. An annual energy analysis shows that 50.9% more in the cooling capacity is required for the adopted under-seat air supply mode to meet higher standard of comfort and indoor air quality with 30 cubic metre per hour per person than that by using a mixing air conditioning system with a common fresh air supply of 15 cubic metre per hour per person. |
| |
Keywords: | national theatre auditorium under-seat air supply displacement ventilation design calculation energy analysis |
本文献已被 CNKI 维普 万方数据 等数据库收录! |