国家大剧院观众厅空调系统和气流组织方式的设计和分析
引用本文:孙敏生,王威,万水娥. 国家大剧院观众厅空调系统和气流组织方式的设计和分析[J]. 暖通空调, 2003, 33(3): 1-8
作者姓名:孙敏生  王威  万水娥
作者单位:北京市建筑设计研究院
摘    要:介绍了观众厅座椅下送风方案。通过对置换通风和空调系统下送风方式的分析和实测,总结出这种气流组织的设计计算方法。全年能耗分析显示,为达到高标准的卫生和舒适要求采用30m^3/h人均新风量的椅下送风空调方式,比15m^3/h人均新风量的混风变新风比空调系统制冷量增加50.9%。

关 键 词:国家大剧院 观众厅 空调系统 气流组织 设计 置换通风 送风
修稿时间:2003-03-17

Design analysis of air conditioning and air distribution in the auditoria of the national theatre
Abstract:Describes the under-seat air supply mode adopted in the project. Provides a procedure of design and calculation based on analyses and field measurement. An annual energy analysis shows that 50.9% more in the cooling capacity is required for the adopted under-seat air supply mode to meet higher standard of comfort and indoor air quality with 30 cubic metre per hour per person than that by using a mixing air conditioning system with a common fresh air supply of 15 cubic metre per hour per person.
Keywords:national theatre   auditorium   under-seat air supply   displacement ventilation   design calculation   energy analysis