变电站钢管塔架多支管空间节点受力性能研究
引用本文:李正良,胡浩,刘红军,张毅,邢海军.变电站钢管塔架多支管空间节点受力性能研究[J].建筑结构学报,2016,37(8):131-142.
作者姓名:李正良  胡浩  刘红军  张毅  邢海军
作者单位:1. 重庆大学 土木工程学院, 重庆 400045; ; 2. 山地城镇建设与新技术教育部重点实验室(重庆大学), 重庆 400045;; 3. 桂林理工大学 土木与建筑工程学院, 广西桂林 541004;; 4. 中国电力科学研究院, 北京 100055
基金项目:国家自然科学基金项目(51278511,51508054),重庆市基础与前沿研究计划项目(cstc2015jcyjA00041)。
摘    要:以青海佑宁750kV变电站塔架的复杂节点为背景,对两类空间多支管梁、柱节点进行了静力加载试验和非线性有限元分析。试验中采用足尺模型,试验装置为具有足够刚度的自平衡框架,制作梁、柱节点试件各2个,采用主动与被动加载相结合的试验加载方案。试验得到了节点的破坏模式、荷载 位移曲线、荷载 应变曲线及受力特性。在此基础上,建立了复杂节点的非线性有限元模型,并对节点的承载性能进行了分析。结果表明:主管部分属于节点的薄弱部位,两类节点都发生了主管凹曲变形破坏,且未出现支管和焊缝的破坏;另外,梁节点两试件出现了支管插板及其加劲板的受压弯曲破坏;加载至设计荷载值时,两类节点所有测点基本处于线弹性工作状态,且节点承载力富余较大,表明节点设计较安全。参数分析表明,主管径厚比 γ 对节点承载力影响显著,支主管直径比β2及厚度比 τ2对节点承载力具有一定影响;梁节点中,γ较小时,β7对节点承载力影响较大;β4、τ4、β5节点板与主管厚度比τJ及插板与主管厚度比τc对各自节点承载力基本无影响。

关 键 词:承载力    多支管空间管节点    钢管结构    静力试验  电力塔架  破坏模式  有限元分析  

Mechanical performance of multiplanar space joints ofsubstation tubular tower
LI Zhengliang,HU Hao,LIU Hongjun,ZHANG Yi,XING Haijun.Mechanical performance of multiplanar space joints ofsubstation tubular tower[J].Journal of Building Structures,2016,37(8):131-142.
Authors:LI Zhengliang  HU Hao  LIU Hongjun  ZHANG Yi  XING Haijun
Affiliation:1. College of Civil Engineering, Chongqing University, Chongqing 400045, China;; 2. Key Laboratory of New Technology for Construction of Cities in Mountain Area (Chongqing University), Ministry of Education, Chongqing 400045, China;; 3. School of Civil and Architectural Engineering, Guilin University of Technology, Guilin 541004, China;; 4. China Electric Power Research Institute, Beijing 100055, China
Abstract:The behavior and bearing capacity of two type multiplanar tubular beam and column joints were investigated via test under static loading in equal proportion and nonlinear finite element analysis, with the background of Youning 750kV transformer substation engineering in Qinghai. Four full-scale specimens, test instrument of self-balancing frame with sufficient stiffness and test scheme of active and passive load were presented. Through analyzing the test results, the failure mode, load-displacement-curve, load-strain curve, and mechanical performance of the joints were obtained. On this basis, the nonlinear finite element models were established and analysis for the complicated joints. The research indicates that the main pipe is a weak part of two type joints, and the concave deformation occurs in their main pipes with no failure in branch ones or welds. In addition, the flexural failure of the flapper and flapper’s stiffener of branch pipe by pressure appears in the beam joints. All measuring points of two type joints are basically kept in linear elastic condition under design loads, and design of joint is very safe with big ability. The results of parametric analysis show that the parameter chord radius to thickness ratio γ has a significant influence on the bearing capacity. Brace to chord diameter ratio β2 and thickness ratio τ2 have some influences on the maximum intensity. β7 has higher impact on the limit strength for small γ value in the beam joints. β4、τ4、β5 gusset plate to chord thickness ratio τJ and inserting plate to chord thickness ratio τc have no impact on the bearing capacity.
Keywords:bearing capacity  failure mode  finite element analysis  multiplanar space tube joint  static test  tubular structure  Keywords: transmission tower  