首页 | 本学科首页   官方微博 | 高级检索  
     

武钢某变电所一段110kV母线全停电事故分析
引用本文:熊友红,寇永江. 武钢某变电所一段110kV母线全停电事故分析[J]. 武钢技术, 2011, 49(4): 47-50
作者姓名:熊友红  寇永江
作者单位:武钢能源试验研究中心,湖北武汉,430081
摘    要:武钢某变电所由于主变穿墙套管CT绝缘损坏和停用线路接地隐患,导致区外故障时110 kV母线差动保护动作,使一段母线全停电。通过该事故进行分析,提出加强二次回路绝缘电阻测试和检查的必要性,防止母差保护误动,并对此次事故应吸取的教训和同类事故预防提出对策。

关 键 词:110kV  母线差动保护  事故预防  对策

Analysis on full power failure of one 110kV bus in a transformer substation in WISCO
XIONG You-hong,KOU Yong-jiang. Analysis on full power failure of one 110kV bus in a transformer substation in WISCO[J]. Wisco Technology, 2011, 49(4): 47-50
Authors:XIONG You-hong  KOU Yong-jiang
Affiliation:XIONG You-hong,KOU Yong-jiang (Energy Test Research Center of WISCO,Wuhan 430081,China)
Abstract:Full power failure of one 110 kV bus occurred in a transformer substation in WISCO because of damage on the CT insulating sleeve of the main transformer and the potential trouble of the disabled ground circuit leading to the differential protection action of 110 kV bus upon occurrence of trouble outside.By analysis of the accident it's pointed out that inspection and test on the secondary loop insulation is of great importance and must be strengthened in order to prevent against accidental differential prot...
Keywords:110 kV  bus differential protection  accident  counter measure  