Constant flow rate charging characteristics of a full-scale stratified chilled water storage tank with double-ring slotted pipe diffusers
Authors:William P. Bahnfleth  Jing Song
Affiliation:aIndoor Environment Center, Department of Architectural Engineering, The Pennsylvania State University, 104 Engineering Unit A, University Park, PA 16802, USA;bBuro Happold Engineers, 105 Chambers Street, 3rd Floor, New York, NY 10007, USA
Abstract:Temperature distributions formed during charging of a 14 m (46 ft) water depth, 7 m (23 ft) radius stratified chilled water storage tank with double ring octagonal slotted pipe diffusers were recorded and analyzed. Prior to the beginning of each test, the tank was fully discharged and at a relatively uniform temperature. To the extent possible, inlet flow rate and temperature were held constant during each test. Six tests were performed for flow rates varying from 50% to 95% of design. Thermal performance was quantified using thermocline thickness, half-cycle figure of merit (FoM1/2) and equivalent lost tank height (ELH). The thermal performance for all tested charge flow rates was good by current standards (FoM1/2 > 90%, ELH < 1 m in all but one case). Thermocline thickness for low and medium flow rates was relatively small, on the order of 1 m (3 ft). Erroneously large thermocline thickness measurements were obtained in the high flow rate case because of the effect of inlet temperature variation combined with the definition used. Significant bulk temperature increase observed below the thermocline in all cases was most likely due to large-scale convection cells driven by the inlet flow. Efforts to improve the performance of diffusers should focus on suppressing this circulation.
Keywords:Thermal energy storage   Slotted pipe diffuser   Stratified tank   Chilled water
本文献已被 ScienceDirect 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号