首页 | 本学科首页   官方微博 | 高级检索  
     


An investigation on friction factors and heat transfer coefficients in a rectangular duct with surface roughness
Authors:Soo Whan Ahn  Kang Pil Son
Affiliation:(1) Department of Mechanical Engineering, Korea University, Seoul, Korea;(2) College of Engineering, School of Mechanical and Automotive Engineering, Catholic University of Daegu, 330 Keum Rak 1-ri, Hayang-Eup, Kyungsan, Kyungbuk, Korea 712-702,;
Abstract:An investigation on the fully developed heat transfer and friction factor characteristics has been made in rectangular ducts with one-side roughened by five different shapes. The effects of rib shape geometries as well as Reynolds numbers are examined. The rib height-to-duct hydraulic diameter, pitch-to-height ratio, and aspect ratio of channel width to height are fixed ate/De=0.0476,P/e=8, andW/H=2.33, respectively. To understand the characteristics of heat transfer enhancements, the friction factors are also measured. The data indicates that the triangular type rib has a substantially higher heat transfer performance than any other ones.
Keywords:
本文献已被 SpringerLink 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号