A new distance relaying algorithm based on complex differential equation for symmetrical components
Authors:Eugeniusz Rosoxllowski  Jan I?ykowski  Bogdan Kasztenny  Murari Mohan Saha
Affiliation:

aThe Technical University of Wrocxllaw (I-8), Wyb. Wyspianskiego 27, 50-370 Wrocllaw, Poland

bABB Network Partner, Västers, Sweden

Abstract:This paper presents a new digital impedance measuring technique for transmission lines that combines symmetrical components and the complex differential equation of an equivalent fault loop circuit. The phase voltages and currents at the relaying point are transformed into symmetrical components using Fourier filters of short window length. Depending on fault type, an appropriate fault loop circuit is formed, signals of which are the appropriate symmetrical components, while a parameter of which is the positive sequence impedance being a geometrical measure of the distance from the relaying point to a fault. The impedance, however, is measured very fast by on-line solving the complex differential equation originated for this fault loop circuit. Consequently, this approach combines frequency domain estimation of symmetrical components (accurate filtration) and time domain measurement of positive sequence impedance (high speed response).

The presented method suits well the protection of parallel lines against high-resistance faults occurring very close to the far end of a line. A new method is proposed for detecting high-resistance faults and deciding which line out of two parallel lines actually suffers a fault.

The included EMTP test results demonstrate the efficiency of the proposed relaying algorithm.

Keywords:Digital protection  Symmetrical components  Fault impedance estimation  Line protection
本文献已被 ScienceDirect 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号