首页 | 本学科首页   官方微博 | 高级检索  
     

500kV断路器取消合闸电阻问题的研究
引用本文:周志芳.500kV断路器取消合闸电阻问题的研究[J].电网技术,1997,21(12):8-11.
作者姓名:周志芳
作者单位:浙江省电力试验研究所!杭州310014
摘    要:本文对浙江北-兰5403线在北仑港侧不装合闸电阻情况下合闸线路时的过电压进行了研究,分析了实测结果及运行情况,还计算了讨论了目前500kV线路绝缘水平下其操作过电压可允许高于2.0pu。并指出输电线路在一定长度范围内,可以取消合闸电阻,而仅用MOA来限制操作过电压。

关 键 词:合闸电阻  断路器  合闸过电压  氧化锌  避雷器

RESEARCH ON ELIMINATING CLOSING RESIST0R FOR 500kV CIRCUIT BREAKERS
Zhou Zhifang.RESEARCH ON ELIMINATING CLOSING RESIST0R FOR 500kV CIRCUIT BREAKERS[J].Power System Technology,1997,21(12):8-11.
Authors:Zhou Zhifang
Abstract:The switching surge overvoltage caused byswitching-on(reclosing) a 5OOkV transmission line is analyzedwhen the closing resistor for circuit breaker at 0ne end of thistransmission line is eliminated. On the basis of calculation it isput forward that under the present insulation condition for5OOkV transmission line the swltching-surge overvoltagehigher than 2. O p. u. is permissible. In a certain range oflength of transmission line the c1osing resistor can be eliminat-ed and the switching-surge overvoltage can be reduced byMOA on1y.
Keywords:Switching-surge overvoltage Closing resistor MOA  
本文献已被 CNKI 维普 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号