首页 | 本学科首页   官方微博 | 高级检索  
     

零序电流互感器配大电阻的配电网单相接地故障检测
引用本文:刘健,刘海,杨晓西,张志华. 零序电流互感器配大电阻的配电网单相接地故障检测[J]. 电测与仪表, 2023, 60(10): 92-97
作者姓名:刘健  刘海  杨晓西  张志华
作者单位:西安科技大学 陕西省电力科学研究院,西安科技大学,陕西省电力科学研究院,陕西省电力科学研究院
基金项目:国家自然科学( U1766208)资助
摘    要:为了简化配电网单相接地故障检测装置的构成和增强单相接地故障特征,探索了一种基于零序电流互感器配较大负载电阻的配电网单相接地故障检测方法。分析了零序电流互感器配大负载电阻时的特性,并通过仿真和实验手段验证了其正确性。在此基础上,研究了二次侧电阻的参数选取问题,探讨了所研究方法在中性点不接地配电网用户侧分界开关单相接地保护装置和变电站单相接地选线装置中的应用,结合典型例子采用数字仿真的方法验证了其可行性,并与传统方法对比分析,结果表明所论述方法在进行单相接地选线时具有故障特征更明显的特点,在实现用户侧单相接地保护时可使电路更简单。

关 键 词:配电网  零序电流互感器  单相接地  继电保护  单相接地选线
收稿时间:2020-09-11
修稿时间:2022-09-05

Single-phase grounding fault detection based on zero sequence current transformer with large secondary resistance
Liu Jian,Liu Hai,Yang Xiaoxi and Zhang Zhihua. Single-phase grounding fault detection based on zero sequence current transformer with large secondary resistance[J]. Electrical Measurement & Instrumentation, 2023, 60(10): 92-97
Authors:Liu Jian  Liu Hai  Yang Xiaoxi  Zhang Zhihua
Affiliation:Shaanxi Electric Power Research Institute,Xi''an University of Science and Technology,Shaanxi Electric Power Research Institute,Shaanxi Electric Power Research Institute
Abstract:To simplify the circuit and increase the fault signature for single-phase grounding faults in neutral ungrounded distribution networks, a single-phase grounding fault detection method based on zero sequence current transformer with large secondary resistance is proposed. The behavior of zero sequence current transformers with large secondary resistance are investigated and verified by simulation and experiment results. Design considerations of the secondary load resistance is given. The applications of the proposed methods in relay protection of the customer circuit breaker and the single-phase grounding line selection in substations are described with typical examples, the feasibility of which is verified by the simulation results. Compared with the traditional approaches, the proposed method makes the detection circuit simpler and increases the fault signature for single-phase grounding line selection in neutral ungrounded distribution networks.
Keywords:distribution network   zero sequence current transformer   single-phase grounding fault   relay protection   single-phase grounding line selection
点击此处可从《电测与仪表》浏览原始摘要信息