首页 | 本学科首页   官方微博 | 高级检索  
     

110 kV架空输电线路复合材料杆塔的材料、电气和机械特性试验
引用本文:邓世聪,刘庭,李汉明,魏前虎,胡广生,刘凯,肖宾. 110 kV架空输电线路复合材料杆塔的材料、电气和机械特性试验[J]. 南方电网技术, 2011, 5(3): 36-40
作者姓名:邓世聪  刘庭  李汉明  魏前虎  胡广生  刘凯  肖宾
作者单位:1. 广东电网公司深圳供电局,广东 深圳,518001
2. 国网电力科学研究院,武汉,430074
摘    要:为了将复合材料杆塔应用于输电线路,以便解决或降低雷击污闪故障问题,有必要进行复合材料杆塔的材料、电气和机械特性试验。试验结果表明,聚氨酯复合材料在受潮、淋雨等条件下仍具有一定的绝缘性,作为杆塔材料可以提高杆塔的绝缘水平;110 kV复合材料杆塔,在地线顺线方向引出、悬空引下接地方式下,与常规铁塔相比,相地间隙增加了70%,相地雷电冲击放电电压增加了约75%,爬电距离增加了约40%以上;在Ⅲ级污秽条件下,相地污秽耐受电压为相地最大工作电压的2.5倍以上;杆塔的整体强度,满足各工况下荷载的要求,杆塔的挠度比常规铁塔大。挂网运行的2基110 kV同杆双回半复合材料杆,在1年多时间的实际运行中情况良好。

关 键 词:复合材料  聚氨酯  输电线路  杆塔  雷击闪络  污闪

Material, Electrical and Mechanical Characteristics Tests of Composite Pole for 110 kV Overhead Transmission Lines
DENG Shicong,LIU Ting,LI Hanming,WEI Qianhu,HU Guangsheng,LIU Kai and XIAO Bin. Material, Electrical and Mechanical Characteristics Tests of Composite Pole for 110 kV Overhead Transmission Lines[J]. Southern Power System Technology, 2011, 5(3): 36-40
Authors:DENG Shicong  LIU Ting  LI Hanming  WEI Qianhu  HU Guangsheng  LIU Kai  XIAO Bin
Affiliation:Shenzhen Power Supply Bureau, Guangdong Power Grid Corporation, Shenzhen, Guangdong 518001, China;State Grid Electric Power Research Institute, Wuhan 430074, China;Shenzhen Power Supply Bureau, Guangdong Power Grid Corporation, Shenzhen, Guangdong 518001, China;Shenzhen Power Supply Bureau, Guangdong Power Grid Corporation, Shenzhen, Guangdong 518001, China;Shenzhen Power Supply Bureau, Guangdong Power Grid Corporation, Shenzhen, Guangdong 518001, China;State Grid Electric Power Research Institute, Wuhan 430074, China;State Grid Electric Power Research Institute, Wuhan 430074, China
Abstract:In order to apply the composite pole to power transmission lines for solving the problems of lightening or polution flashover, it is necessary to test its material, electrical and mechanical characteristics. The test results in this paper are as following: the polyurethane composite can remain its insulativity somehow under the condition of damp or raining, and it can be used for pole to increase the insulation level; the composite pole for 110 kV lines is better than the normal steel tower as its phaseground clearance is higher of 70%, and its lightning impulsive voltage increases about 75% , as well as its creepage distance of phaseground increases about 40% in the grounding way of groundingwire extracting along the line direction and going off the tower down to the ground; the phaseground tolerance voltage of pollution flashover is 2.5 times more than the maximum working voltage; the whole strength of pole can meet the requirements in various load conditions, and its deflection is larger than that of the steel pole. A 110 kV double circuits halfcomposite pole with two bases has been oprating in network for more than one year well enough.
Keywords:composite materials   polyurethane   transmission line   pole   lightning flashover   pollution flashover
本文献已被 CNKI 维普 万方数据 等数据库收录!
点击此处可从《南方电网技术》浏览原始摘要信息
点击此处可从《南方电网技术》下载全文
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号