首页 | 本学科首页   官方微博 | 高级检索  
     

基于CONE的超高温耐火电缆火灾危险性分析
引用本文:陈善求,赵雯筠,颜龙,欧阳罕贞.基于CONE的超高温耐火电缆火灾危险性分析[J].消防科学与技术,2022,41(2):156-160.
作者姓名:陈善求  赵雯筠  颜龙  欧阳罕贞
作者单位:(1.金杯电工股份有限公司,湖南 长沙410205;2. 中南大学 防灾科学与安全技术研究所,湖南 长沙410075)
基金项目:国家自然科学基金项目(51906261);湖南省战略性新兴产业科技攻关与重大科技成果转化项目(2019GK4035)。
摘    要:利用锥形量热仪对超高温耐火电缆在不同辐射功率下的点燃时间(TTI)、热释放速率(HRR)、质量损失速率(MLR)和燃烧残余物进行了研究。研究表明,随着辐射功率增加,耐火电缆的TTI逐渐缩短,HRR和MLR逐渐增大,火灾危险性逐渐增加。超高温耐火电缆在35 kW/m2和50 kW/m2辐射功率下火灾性能指数相比于25 kW/m2分别增加了44.4%和176.5%,火灾增长指数分别增加了30.4%和83.0%。结合理论分析可以得出,耐火电缆的临界辐射功率为3.61 kW/m2、零辐射平均热释放速率为36.5 kW/m2,表现出较低的火灾危险性。

关 键 词:超高温耐火电缆  锥形量热仪  热释放速率  点燃时间  火灾危险性  

Study on fire risk of ultra-high temperature fireresistant cable based on cone calorimeter test
Affiliation:(1. Gold cup Electric Apparatus Co., Ltd., Hunan Changsha 410205, China; 2. Institute of Disaster Prevention Science and Safety Technology, Central South University, Hunan Changsha 410075, China)
Abstract:The ignition time,heat release rate,mass loss rate and combustion residue of ultra-high temperature fire-resistant cable under different external heat flux were analyzed via the cone calorimeter test.The results show that with the increase of external heat flux,the ignition time of cables is gradually shortened,the heat release rate and mass loss rate are gradually increased,so does the fire risk.The fire performance indexes of fire-resistant cables at the external heat flux of 35 and 50 kW/m2 increased by 44.4%and 176.5%,respectively,and the fire growth indexes increased by 30.4%and 83.0%,respectively,compared to those of 25 kW/m2.Combined with theoretical analysis,it can be concluded that the fire-resistant cable has the critical heat flux of 3.61 kW/m2 and average limiting heat release rate of 36.5 kW/m2,showing a low fire risk.
Keywords:ultra-high temperature fire-resistant cable  cone calorimeter  heat release rate  time to ignition  fire risk
本文献已被 维普 等数据库收录!
点击此处可从《消防科学与技术》浏览原始摘要信息
点击此处可从《消防科学与技术》下载全文
设为首页 | 免责声明 | 关于勤云 | 加入收藏