Effects of intermediate pressure on the heating performance of a heat pump system using R410A vapor-injection technique |
| |
Authors: | Chul Woo RohMin Soo Kim |
| |
Affiliation: | Division of WCU Multiscale Mechanical Design, School of Mechanical & Aerospace Engineering, Seoul National University, Seoul 151 744, Republic of Korea |
| |
Abstract: | Recent heat pumps are actively equipped with a refrigerant vapor-injection technique to acquire better performance in severe operating conditions. In this study, the target system which has an additional expansion valve at the outlet of condenser was presented. The concept of intermediate pressure was generated in the target system. Effects of the intermediate pressure on the heating performance with various injection ratios were measured and analyzed according to the compressor frequencies ranging from 60 to 100 Hz. Unlike conventional vapor-injection cycle, the maximum injection ratio was highly affected by the intermediate pressure. The high intermediate pressure provided high initial heating capacity and COP; but it restricted the available range of vapor-injection within narrow limits. The result indicates that a proper operating strategy is needed for the vapor-injection cycle. |
| |
Keywords: | COP Experimentation Heat pump Injection Performance R410A |