首页 | 本学科首页   官方微博 | 高级检索  
     

Natural Ventilation by Air Captors and Extractors Sheds in Hospitals in Brazil: Wind Tunnel Measurements
基金项目:Acknowledgments The authors would like to acknowledge FAPESP (State of Sgo Paulo Research Foundation) for the financial support provided to this research.
摘    要:Natural ventilation is an efficient design strategy for the passive cooling of buildings, especially in tropical countries such as Brazil. Among the ventilation strategies, sheds can be highlighted. These structures consist of roof openings that work as air captors or extractors depending on their location in relation to the prevailing wind directions. The hospitals of the Sarah Network, designed by the Brazilian architect Joao Filgueiras Lima, Lele, are worldwide known for using these elements to improve natural ventilation. This paper analyses the natural ventilation performance of sheds for air collecting and extracting in two Sarah hospitals located in the cities of Salvador and Rio de Janeiro. In each building, the sheds were analyzed for air extracting and collecting. The analyses were carried out by reduced physical models in an atmospheric boundary layer wind tunnel. The wind velocity was measured at external and internal points of the buildings, using hot-wire anemometers. The results show that the wards in Rio de Janeiro hospital are 17% more ventilated than the ones in the Salvador hospital. However, this difference occurs not only because of the collecting sheds but also because of set of openings and the configuration of the covering in hospitals in Rio de Janeiro.

关 键 词:医院病房  自然通风  提取器  风洞测量  巴西  里约热内卢  大气边界层风洞  航空
本文献已被 维普 等数据库收录!