基于非最严苛电网运行方式的超高压线路距离保护整定方法
引用本文:李怀强,高 露,粟小华,胡 勇,盛志文,石东源. 基于非最严苛电网运行方式的超高压线路距离保护整定方法[J]. 电力系统保护与控制, 2020, 48(21): 166-172. DOI: 10.19783/j.cnki.pspc.200096
作者姓名:李怀强  高 露  粟小华  胡 勇  盛志文  石东源
作者单位:国家电网西北电力调控分中心,陕西 西安710048;国网西安供电公司,陕西 西安710032;华中科技大学,湖北 武汉 430074
基金项目:国家自然科学基金项目资助(51777081)
摘    要:分析了西北电网三起因保护拒动而导致的故障范围扩大事故,指出现有基于最严苛电网运行方式的超高压线路后备保护整定可能导致保护定值灵敏性不足、无法可靠动作的问题。提出了基于非最严苛电网运行方式的超高压线路距离保护整定方法,距离II段采用接近于实际的检修方式进行整定,距离III段采用考虑对侧故障可靠切除后的运行方式进行整定。该整定方法在改善配合关系的同时,能够最大限度地发挥距离保护对本线和相邻设备的后备作用。实际算例验证了该整定方法的有效性。

关 键 词:距离保护  后备保护  整定计算  配合  超高压线路
修稿时间:2020-05-07

A distance protection relay coordination method for EHV transmission lines based on non most severe grid operation mode
LI Huaiqiang,GAO Lu,SU Xiaohu,HU Yong,SHENG Zhiwen,SHI Dongyuan. A distance protection relay coordination method for EHV transmission lines based on non most severe grid operation mode[J]. Power System Protection and Control, 2020, 48(21): 166-172. DOI: 10.19783/j.cnki.pspc.200096
Authors:LI Huaiqiang  GAO Lu  SU Xiaohu  HU Yong  SHENG Zhiwen  SHI Dongyuan
Abstract:This paper analyzes three power grid fault range enlargement accidents in the Northwest Power Grid caused by the failure of protection to operate on command. It is pointed out that one of the reasons for this is the insufficient sensitivity of line protection setting because of the existing backup protection coordination method which is based on extreme grid operation modes. A method for coordinating the settings of distance protection for extra-high-voltage lines based on non-extreme grid operation modes is proposed. In this method, zone II of the distance protection is coordinated based on modes close to actual maintenance situations, while zone III is coordinated using the mode where the opposite-side fault is successfully removed. This method can clarify the coordination relationship of adjacent relays and thus optimize a relay''s backup protection function for the line where it is installed and its downstream equipment. The effectiveness of the proposed method is verified through experiments. This work is supported by National Natural Science Foundation of China (No. 51777081).
Keywords:distance protection   backup protection   setting calculation   coordination   ultra-high voltage transmission line