UPS系统中电压型逆变器开路故障诊断研究
引用本文:李江伟,石瑞才,王 愚,李绍坚,杨 鹏,鲍海波. UPS系统中电压型逆变器开路故障诊断研究[J]. 电力系统保护与控制, 2020, 48(23): 148-153. DOI: 10.19783/j.cnki.pspc.200067
作者姓名:李江伟  石瑞才  王 愚  李绍坚  杨 鹏  鲍海波
作者单位:广西电网有限责任公司南宁供电局,广西 南宁 530229;广西电网有限责任公司南宁宾阳供电局,广西 南宁 530229
基金项目:国家自然科学基金项目资助(51507002);广西电网有限责任公司科技项目资助(GXKJXM20180433)
摘    要:逆变器开路故障是不间断电源(Uninterruptible Power Supply, UPS)系统中一种常见故障,它会降低电能质量,甚至会引起其他部件的潜在二次故障。研究有效的逆变器故障诊断技术对提高UPS系统的可靠性具有重要意义。因此,采用基于绝对归一化的Park矢量法实现逆变器开路故障诊断。利用相电流的平均值与相电流绝对值的平均值的归一化量诊断和定位单个或两个开关管开路故障。利用相电流绝对值的平均值与Park矢量模的归一化量诊断同一桥臂的两个开关管开路故障,该方法可以有效地实现开路故障检测和故障定位。最后基于Matlab/Simulink对提出的故障诊断方法进行验证,仿真结果表明了所提出故障诊断方法的有效性。

关 键 词:UPS系统  开路故障  故障诊断
收稿时间:2020-01-15
修稿时间:2020-02-28

Open-circuit fault diagnosis of a voltage-source inverter in a UPS system
LI Jiangwei,SHI Ruicai,WANG Yu,LI Shaojian,YANG Peng,BAO Haibo,SHI Ruicai,WANG Yu,LI Shaojian,YANG Peng,BAO Haibo. Open-circuit fault diagnosis of a voltage-source inverter in a UPS system[J]. Power System Protection and Control, 2020, 48(23): 148-153. DOI: 10.19783/j.cnki.pspc.200067
Authors:LI Jiangwei  SHI Ruicai  WANG Yu  LI Shaojian  YANG Peng  BAO Haibo  SHI Ruicai  WANG Yu  LI Shaojian  YANG Peng  BAO Haibo
Affiliation:1. Nanning Power Supply Bureau, Guangxi Power Grid Co., Ltd., Nanning 530229, China;2. Binyang Power Supply Bureau, Guangxi Power Grid Co., Ltd., Nanning 530229, China
Abstract:The open-circuit fault in an inverter is a common fault in an Uninterruptible Power Supply (UPS) system. It can reduce power quality and even cause potential secondary faults in other components. It is of great significance to study effective fault diagnosis technology of inverters to help improve the reliability of a UPS system. Therefore, the Park vector method based on absolute normalization is used for open-circuit fault detection of the inverter. The normalized value between the average value of phase current and the average value of the absolute value of phase current is used to diagnose and locate an open-circuit fault of a single or two switches. The normalized value between the average value of the absolute value of phase current and the Park vector module is used to diagnose the open-circuit fault of two switches of the same bridge arm. This method can effectively realize fault detection and fault location. Finally, the proposed fault diagnosis method is verified using Matlab/Simulink. The simulation results show the effectiveness of the proposed fault diagnosis method.This work is supported by National Natural Science Foundation of China (No. 51507002) and Science and Technology Project of Guangxi Power Grid Co., Ltd. (No. GXKJXM20180433).
Keywords:UPS   open circuit fault   fault diagnosis