首页 | 本学科首页   官方微博 | 高级检索  
     


Modelling of the coefficient of performance of an air-cooled screw chiller with variable speed condenser fans
Authors:FW Yu  KT Chan
Affiliation:Department of Building Services Engineering, The Hong Kong Polytechnic University, Hung Hom, Kowloon, Hong Kong, China
Abstract:Air-cooled chillers are generally recognized as energy intensive equipment in air-conditioned buildings in the subtropical climate. This paper considers how the use of variable speed condenser fans enables these chillers to operate more efficiently. The thermodynamic model of an air-cooled screw chiller was developed using the simulation program TRNSYS and validated using the field data and specifications of the chiller. The staging of condenser fans and the control of their speed in various operating conditions were described. A comparison was made on the coefficient of performance of the chiller in the steady state with various control strategies: head pressure control with constant or variable speed condenser fans; condensing temperature control (CTC) with constant or variable speed condenser fans. Potential improvements in the chiller COP due to the use of CTC with variable speed condenser fans were discussed. The findings of this paper are useful in developing more energy efficient air-cooled chillers.
Keywords:Air-cooled screw chiller  Coefficient of performance  Condenser fans  Variable speed control
本文献已被 ScienceDirect 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏