首页 | 本学科首页   官方微博 | 高级检索  
     


Life cycle analysis of enhanced condenser features for air-cooled chillers serving air-conditioned buildings
Authors:FW Yu  KT Chan
Affiliation:Department of Building Services Engineering, The Hong Kong Polytechnic University, Hung Hom, Kowloon, Hong Kong, China
Abstract:Air-cooled chillers are commonly used to provide cooling energy for air-conditioned buildings at the expense of considerable electricity. This paper examines the life cycle electricity cost of these chillers with the improved condenser features of condensing temperature control (CTC), evaporative pre-coolers (EC) and variable speed condenser fans (VSF). A validated model for an air-cooled screw chiller was used to ascertain how the individual and mixed features influence the annual electricity consumption of chillers in various operating conditions. It is estimated that the life cycle electricity cost savings range from HK$ 2,099,742 with EC to HK$ 6,399,564 with all the three features, with regard to a chiller plant serving an office building for 15 yr. The life cycle analysis reported here provides important insights into how to reap the benefits of energy efficient technologies for air-cooled chillers.
Keywords:Air-cooled chiller  Condensing temperature control  Evaporative pre-coolers  Life cycle analysis  Variable speed condenser fans
本文献已被 ScienceDirect 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号