首页 | 本学科首页   官方微博 | 高级检索  
     

多跨覆冰导线脱冰振动模型风洞试验研究
引用本文:刘敏,晏致涛,冯上铭,游溢.多跨覆冰导线脱冰振动模型风洞试验研究[J].振动与冲击,2018,37(3):223-229.
作者姓名:刘敏  晏致涛  冯上铭  游溢
作者单位:1.重庆大学土木工程学院,重庆,400044
2.重庆科技学院建筑工程学院,重庆 401331
3. 国网新疆电力公司电力科学研究院,乌鲁木齐 830011
摘    要:覆冰导线脱冰可能造成金具、导线和杆塔等构件受力破坏,也可能会引起导线闪络、烧断等电力事故。设计了1∶50的三跨覆冰导线的缩尺模型,采用熔断集中荷载的方法模拟导线脱冰,共七种工况研究三跨导线中脱冰量、脱冰跨位置、覆冰厚度和风速等参数不同时,导线的冰跳高度、导线张力和绝缘子轴力变化规律。结果表明:边跨脱冰将引起比中间跨脱冰更大的竖向振动,跳跃高度增大了近7%,导线张力也有明显增大;在风荷载作用时,导线脱冰振动会受气动阻尼影响,跳跃高度和振动周期都有所减小,导线张力和悬垂绝缘子的轴力随着风荷载增大而增大。

关 键 词:覆冰导线    脱冰    模型试验    风洞    振动  

Wind tunnel model tests for ice-shedding vibration of multi-span icing conductors
LIU Min,YAN Zhi-tao,FENG Shang-ming,YOU Yi.Wind tunnel model tests for ice-shedding vibration of multi-span icing conductors[J].Journal of Vibration and Shock,2018,37(3):223-229.
Authors:LIU Min  YAN Zhi-tao  FENG Shang-ming  YOU Yi
Affiliation:1.School of Civil Engineering, Chongqing University, Chongqing 400045, China; 2. School of Civil Engineering, Chongqing University of Science & technology, Chongqing 401331, China; 3. State Grid Xinjiang Electric Power Company Electric Power Research Institute, Urumqi 830011, China
Abstract:Icing conductors’ ice-shedding may lead to damages of end fittings, wires and towers, and even tower collapse and other machinery accidents. A three-span 1:50 scale model tests for icing conductors were conducted to obtain conductor’s ice-jump height, conductor’s tension force and axial force changes of insulators. In tests, ice-shedding loads were simulated with suddenly dropping dead-weights from conductors. Seven ice-shedding cases were studied with different magnitudes of ice-shedding, positions of ice-shedding span, ice thicknesses and wind velocities, etc. The results showed that conductor side-span ice-shedding causes larger vertical vibration than mid-span ice-shedding does, conductor’s jumping height increases by near 7% and conductor’s tension force rises obviously; when there are wind loads, conductor’s ice-shedding vibration is affected by aerodynamic damping, conductor’s jumping height and vibration period become smaller, conductor tension force and insulator axial force increase with increase in wind loads.
Keywords:icing conductor                                                      ice-shedding                                                      model test                                                      wind tunnel                                                      vibration
本文献已被 CNKI 等数据库收录!
点击此处可从《振动与冲击》浏览原始摘要信息
点击此处可从《振动与冲击》下载全文
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号