一起跳闸线圈烧坏导致备自投误动的事故分析
引用本文:李文书.一起跳闸线圈烧坏导致备自投误动的事故分析[J].江苏电机工程,2011,30(1):14-15,19.
作者姓名:李文书
作者单位:南京供电公司,江苏,南京,210008
摘    要:为保证对重要用户可靠供电,在终端变电站中常配有备自投装置.但若备自投方案中存在缺陷,则可能因备自投误动而导致全站失电.结合禄口变35 kV备自投误动案例,分析了误动原因,并提出合理建议,即采用双节点替代单节点遥信、或采用开关辅助接点信号来判别开关位置,可有效避免因跳(合)闸线圈烧坏而诱发的备自投误动.

关 键 词:备自投  遥信  跳闸位置

Analysis of Mal-operation Occurred in Busbar Automatic Transfer Switch for the Breaking Coil Burned
LI Wen-shu.Analysis of Mal-operation Occurred in Busbar Automatic Transfer Switch for the Breaking Coil Burned[J].Jiangsu Electrical Engineering,2011,30(1):14-15,19.
Authors:LI Wen-shu
Affiliation:LI Wen-shu(Nanjing Power Supply Company,Nanjing 210008,China)
Abstract:In order to ensure the reliable power supply for VIP customers,busbar automatic transfer equipments are generally used in terminal substations.If the busbar automatic transfer switch is not configured properly,its mal-operation may cause the whole substation power-off.After analyzing the reasons for mal-operation accident occurred in the Lukou substation,it is brought forward that using double-node remote communication to replace the single-node,or using the auxiliary node of breakers to distinguish the swi...
Keywords:busbar automatic transfer switch(BATS)  remote communication  trip position  