首页 | 本学科首页   官方微博 | 高级检索  
     


A novel solar bi-ejector refrigeration system and the performance of the added injector with different structures and operation parameters
Authors:Fei Wang  Shengqiang Shen
Affiliation:Key Laboratory of Sea Energy Utilization and Energy Conservation of Ministry of Education, Dalian University of Technology, Dalian 116024, China
Abstract:A novel solar bi-ejector refrigeration system was investigated, whose difference compared to the traditional system is that the circulation pump is replaced by a thermal injector. The new system works more stably and needs less maintenance work than the old one, and the whole system can more fully utilize the solar energy. The mathematical models for calculating the performance of the injector and the whole solar refrigeration system were established. The pressure rise performance of injector under different structure and operation parameters and the performance of solar bi-ejector refrigeration system were studied with R123. The results show that the discharged pressure of injector is affected by structure dimensions of injector and operation conditions. With increasing generation temperature, the entrainment ratio of ejector becomes better while that of injector becomes worse and the overall thermal efficiency of the solar bi-ejector refrigeration system first increases and then decreases with an optimum value of 0.132 at generation temperature of 105 °C, condensation temperature of 35 °C and evaporation temperature of 10 °C.
Keywords:Solar  Bi-ejector refrigeration  Injector  Performance  Thermal efficiency