An experimental study on ice formation around horizontal long tubes |
| |
Authors: | Badr A Habeebullah |
| |
Affiliation: | aMechanical Engineering Department, Faculty of Engineering, King Abdulaziz University, P.O. Box 80204, Jeddah 21589, Saudi Arabia |
| |
Abstract: | The results of an experimental study are presented where the growth rate of ice on the outside of cooled copper tubes was studied. The tubes, which were immersed in water in an insulated vessel, were internally cooled by circulating glycol through them.It was found that axial growth rate of ice is distinct at low values of the coolant Reynolds number and short freezing times. The slope of the ice thickness with axial distance showed moderate dependency on time but varied with coolant flow rate, and with Stanton and Biot numbers.A key result from the experiments is the abrupt ice thickness enlargements on the surface of tube bends. This anomaly may be attributed to internal flow disturbances of the coolant, and creation of local eddies inside the bends that enhance growth of ice. The effect was evident for a low Reynolds number (Re = 251.9 and Bi < 1), and fades out for large Reynolds number flows. |
| |
Keywords: | Thermal storage Ice tank Horizontal tube Copper Experiment Growth IceMots clé s: Accumulation thermique Bac à glace Tube horizontal Cuivre Expé rimentation Croissance Glace |