首页 | 本学科首页   官方微博 | 高级检索  
     

重庆某医院中央空调系统改造及评估
引用本文:刘一隆,吕刚.重庆某医院中央空调系统改造及评估[J].重庆建筑,2016(1):9-12.
作者姓名:刘一隆  吕刚
作者单位:重庆旅舟科技有限公司,重庆,400000
摘    要:该文以重庆市某医院为对象,对医院进行用能设备统计和能源审计,得到该建筑单位面积能耗为136.82k Wh/m~2·a,计算建筑分类能源占比及逐月用电量,分析存在的问题,锁定该建筑的主要节能改造目标在中央空调系统,结合测试数据计算空调系统各部分能耗值及比例,确定改造手段为主机加装智能控制装置、水泵变频、冷却塔自控进行改造,医院改造后空调系统节能率达39.85%,占建筑总用电量的8.96%,相当于节省40.73万元的经济效益。

关 键 词:医院建筑  空调系统  智能控制  水泵变频  节能率

Renovation and Evaluation of Central Air-conditioning system of A Hospital in Chongqing
Abstract:Taking a hospital in Chongqing as a case study, the energy-consuming equipment are counted with energy audited, it's obtained that the energy consumption per unit area is 136.82kW·h/㎡·a, and the classified building energy proportion and monthly electricity consumption are calculated to ana-lyze the existing problems. The major renovation goal, thus, for the building energy saving is central air-conditioning system. Combined with the test statistics, the energy consumption value and proportion of each part of the air-conditioning system are calculated, so as to determine the right renovation scheme to install the intelligent trip device, water pump frequency conversion and cooling tower automation. The renovated air-conditioning system has the energy efficiency of 39.85%, a proportion of 8.96% in total electricity consumption of the building, saving up to 407,300 yuan for economic benefit.
Keywords:hospital building  air-conditioning system  intelligent control  water pump frequency conversion  energy saving rate
本文献已被 CNKI 万方数据 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号