Condensate retention on a louver-fin-and-tube air cooling coil |
| |
Authors: | Xiangguo Xu Chunwah Leung Mingyin Chan Shiming Deng |
| |
Affiliation: | aDepartment of Building Services Engineering, The Hong Kong Polytechnic University, Kowloon, Hong Kong SAR, China;bDepartment of Mechanical Engineering, The Hong Kong Polytechnic University, Kowloon, Hong Kong SAR, China |
| |
Abstract: | This paper presents a study of condensate retention on a louver-fin-and-tube air cooling coil, which is commonly used in air conditioning (A/C) systems. Compared to previously related work focusing on the influence of condensate retention on the heat and mass transfer between air and a cooling coil, the present study emphasizes the impacts of operating parameters on condensate retention on a cooling coil. A new method to describe the steady-state condensation has been suggested and a new mathematical model to represent the force balance of retained condensate developed. The mass of condensate retained has been measured experimentally under various operating conditions of a direct expansion (DX) air cooling and dehumidification system. The influences of air dry-bulb temperature, moisture content and Reynolds Number on condensate retention are discussed. The model developed relates the mass of condensate retained to condensing rate, and is successful in predicting the trends of condensate retention under normal operating conditions for air cooling applications. |
| |
Keywords: | Air conditioning Heat exchanger Air cooler Finned tube Louver Experiment Modeling Condensation Vapour WaterMots clé s: Conditionnement d'air É changeur de chaleur Refroidisseur d'air Tube aileté Persienne Expé rimentation Modé lisation Condensation Vapeur Eau |
本文献已被 ScienceDirect 等数据库收录! |
|