首页 | 本学科首页   官方微博 | 高级检索  
     

按单相短路保护灵敏度确定低压配电距离
引用本文:雍静.按单相短路保护灵敏度确定低压配电距离[J].建筑电气,2000,19(2):3-8.
作者姓名:雍静
作者单位:重庆建筑大学,400045
摘    要:通过分析和计算得出:在单级配电的情况下,配电线路若能满足单相短路保护灵敏度条件则一定满足电压损失条件;在二级配电的情况下,大多数仍满足上述关系。文中还提出了低压系统中只用正序阻抗表达的单相短路电流的简化计算公式。

关 键 词:单相短路  灵敏度  电压损失  配电距离  配电系统

Determination of Low Voltage Line Distribution Distance by means of Single Phase Short-circuit Protection Sensitivity
Yong Jing.Determination of Low Voltage Line Distribution Distance by means of Single Phase Short-circuit Protection Sensitivity[J].Building Electricity,2000,19(2):3-8.
Authors:Yong Jing
Affiliation:Yong Jing ;(Chongqing Jianzhu University 400045 China)
Abstract:According to analysis ari calulalion, to distribution distance of single stage line, loss of v Jtage is satisfied if single phase short-circuit protection sensitivity is satisfied; to distribution distance of two stages line, in most conditior 3, above conclusion is right. In the paper, the reduced single phase short-circuit current equation expressing as positive sequence impi dance only is showed.
Keywords:Single phase short-circuit  Sensitivity  Loss of voltage  Distribution distance