首页 | 本学科首页   官方微博 | 高级检索  
     

OPGW覆冰断线原因分析
引用本文:冀晋川,高义斌,董勇军,李青,王晨宝. OPGW覆冰断线原因分析[J]. 华北电力技术, 2008, 0(7)
作者姓名:冀晋川  高义斌  董勇军  李青  王晨宝
作者单位:山西电力科学研究院,山西太原,030001
摘    要:对OPGW覆冰断线原因进行了分析,认为覆冰断线原因是OPGW覆冰致使其弧垂加大,使其与导线处于同一高度或低于导线高度,这样在风的激励下诱发覆冰OPGW舞动,导致导线对OPGW放电产生高温电弧,将外层部分铝合金绞线熔断,使其余绞线不足以承受OPGW的张力,最终导致OPGW断线。

关 键 词:复合光缆  覆冰  弧垂  舞动

Reason Analysis of OPGW Breakage Caused by Ice Cover
Ji Jin-chuan,Gao Yi-bin,Dong Yong-jun,Li Qing,Wang Chen-bao. Reason Analysis of OPGW Breakage Caused by Ice Cover[J]. North China Electric Power, 2008, 0(7)
Authors:Ji Jin-chuan  Gao Yi-bin  Dong Yong-jun  Li Qing  Wang Chen-bao
Abstract:This paper analyzed the cause of OPGW breakage caused by ice cover,it considers the main cause of breakage is that the ice cover on OPGW results in the increasing of sag,the sagged OPGW reached to the height of conductors or lower than their height, and also OPGW icing gallops under wind, the high-temperature electric arc produced by the discharge of conductors to OPGW fuses a part of the outer aluminium alloy stranded wires,and remainders are not capable to endure tension of OPGW,which results in breaking OPGW at last.
Keywords:OPGW  ice cover  sag of the span  galloping
本文献已被 CNKI 维普 万方数据 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号